Company requires the installation of a 5000-gallon double walled fuel tank outside of building 2370-HVC (Figures 1-2) that is compatible with 100% bio diesel and can maintain fluid temperature above 50 °F (10 °C) to prevent clouding. Seller will design a system capable of maintaining the bio diesel at the required temperatures while continually circulating the fuel between a generator that is ~100 feet away and back to 5000-gallon tank (Figure 3). There is an existing covered trench in the roadway to allow fuel lines to transverse this 100 feet. Tees in the fuel line will be needed allow fuel to flow to and from the genset, and shutoff valves will be needed between the recirculating fuel line and the genset. Additionally, shutoff valves will need to be located at the exit of the 5000-gallon tank. - See SOW for more detail.